Features AT175F1031 • Rated at 75 VA. • Color-coded leadwires for primary connections and screw terminals for secondary connections, fixed 1/4 inch (6 mm) male quick-connects or color-coded leadwires for both primary and secondary, are standard. • Meet NEC Class 2 requirements. • Meet Underwriters Laboratories Inc. Standard UL 1585 and are identified. Class 2 not wet, Class 3 wet. Product Specifications Back To Top Description Plate or panel mounted 208/277/480 Vac Transformer with 9 in. lead wires and button for manually resetting the circuit breaker and metal end bells. Electrical Ratings -Primary Voltage 208 Vac, 277 Vac, 480 Vac Electrical Ratings -Secondary Voltage 27.5 V.O.C. Frequency 60 Hz Mounting Includes 1/2 14 NPSM conduit connector and lock nut for mounting on plate or panel (not included) with 7/8 in. knockout, and feet for surface mount. Electrical Connections (Primary)(in.) 9 in. leadwires with all leadwires through conduit screw Electrical Connections (Primary)(mm) 229 mm leadwires with all leadwires through conduit screw. Electrical Connections (Secondary)(in.) 9 in. leadwires with all leadwires thru conduit screw Electrical Connections (Secondary)(mm) 229 mm leadwires with all leadwires thru conduit screw Electrical Ratings -Output 24 Vac at 75 VA Dimensions (in.) 3 3/16 in. high x 2 3/16 in. wide x 3 15/16 in. deep Dimensions (mm) 81 mm high x 56 mm wide x 102 mm deep Temperature Ratings (F) -20 F to +105 F Temperature Ratings (C) -29 C to +41 C Approvals, Underwriters Laboratories Inc UL Listed: File no. E14881, Guide no. XOKV. Approvals, Canadian Standards Association Certified: File No. LR95329-18 Includes Button for manually resetting the circuit breaker and metal end bells. Tradeline Value Tradeline
|
|