Totally enclosed Micro Switch snap-acting switches operate on temperature rise to setpoint. Visible control point scale and external adjustment screw permit easy setting. Horizontal or vertical insertion of the sensing element. Direct or well immersion of the sensing element. Models available for strap-on mounting. Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications. TRADELINE models include heat-conductive compound. Select models have wells. Product Specifications Back To Top Description Circulator Control, High Limit or Low Limit Aquastat Controller with 65 F to 200 F operating temperature and 5 F to 30 F adj. Differential Application Circulator Control and High Limit or Low Limit Bulb Size (in.) 3/8 in. x 2 7/8 in. copper Bulb Size (mm) 10 mm x 73 mm copper Switching Action SPDT Operating Temperature Range (F) 65 F to 200 F Operating Temperature Range (C) 18 C to 93 C Electrical Ratings (millivolt) 0.25 A @ 0.25 to 12 Vdc Electrical Ratings (AFL) 8A @ 120 Vac Electrical Ratings (AFL) 5.1A @ 240 Vac Electrical Ratings (ALR) 48A @ 120 Vac Electrical Ratings (ALR) 30.6A @ 240 Vac Differential Temperature (F) 5 F to 30 F adj. Differential Temperature (C) 3 C to 17 C adj. Maximum Ambient Temperature (F) 150 F Maximum Ambient Temperature (C) 66 C Case Dimensions (in.) 5 5/8 in. high x 2 in. wide x 2 3/4 in. deep Case Dimensions (mm) 143 mm high x 51 mm wide x 70 mm deep Mounting Horizontal or Vertical or Strap-on-mounting Approvals, Underwriters Laboratories Inc UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2 Approvals, Canadian Standards Association Certified: File No. LR95329-1 Tradeline Value Tradeline
|
|