Features L8148E1265 • High limit opens burner circuit only. • Include transformer and accessory terminals for adding a remote low limit controller. • Case available for horizontal or vertical mounting. • Requires a 24 Vac thermostat with heat anticipator set at 0.2A. • TRADELINE models include well adapter, tube of heat conductive compound and range stops. Product Specifications Back To Top Description High Limit Aquastat Relay with 15 F fixed differential Application High Limit Operating Range, High Limit (F) 180 F to 240 F Operating Range, High Limit (C) 100 C to 133 C Differential Temperature (F) 15 F fixed Switching Action SPST: High Limit & Circulator Anticipator Setting 0.2 A Maximum Safe Operating Pressure (psi) Immersion Well: 255 psi Maximum Safe Operating Pressure (kPa) Immersion Well: 1757 kPa Electrical Ratings (ALR) 44.4A @ 120 Vac Electrical Ratings (ALR) 22.2A @ 240 Vac Electrical Ratings 0.25 A @ 0.25 to 12 Vdc Electrical Ratings (burner AFL) Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 Vac Electrical Ratings (burner AFL) Low Voltage: 0.8 A max. @ 24 Vac Electrical Ratings (burner ALR) Line Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac Electrical Ratings (burner millivolt) 0.25 A @ 1/4 to 12 Vdc Electrical Ratings (circulator AFL) 3.7 A @ 240 Vac Electrical Ratings (circulator AFL) 7.4 A @ 120 Vac Electrical Ratings (circulator ALR) 44.4 A @ 120 Vac Electrical Ratings (circulator ALR) 22.7 A @ 240 Vac Voltage 120 Vac Frequency 60 Hz Capillary Length (in.) 4 1/2 in. Capillary Length (mm) 114 mm Dimensions (in.) 6 1/8 in. high x 4 5/16 in. wide x 3 1/8 in. deep Dimensions (mm) 156 mm high x 110 mm wide x 79 mm deep Insulation Depth (in.) 1 1/2 in. to 3 in. less well. Insulation Depth (mm) 38 mm to 76 mm less well Mounting Vertical Mount Operating Humidity Range (% RH) 0 to 95% RH, non-condensing Maximum Ambient Temperature (F) 150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load Maximum Ambient Temperature (C) 66 C with 1.2 A 24 V load; 25 C with 1.4 A 24 V load Electrical Connections Quick-Connect / Screw Approvals, Underwriters Laboratories Inc UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2. Approvals, Canadian Standards Association Certified: File No. LR95329-1 Includes Molex® plug for use with vent damper, includes heat-conductive compound. Includes Molex(r) plug for use with vent damper, includes heat-conductive compound. Tradeline Value Tradeline
|
|