Product Specifications R7184U1020 Description Electronic Oil Primary 10 in. leads, 45 seconds lock out timing and selectable valve and blower delays Ignition Type Interrupted Lead Length (in.) 10 in. Lead Length (mm) 254 mm Timing, Safety Switch 45 sec. Mounting Bracket Mounts on standard 4X 4 in. junction box. Electrical Connections Burner motor, oil valve, ignition, cad cell, limit, thermostat, alarm Electrical Rating; Contacts (full load) 7.4 A @ 120 Vac; 3.7 a @ 240 Vac Electrical Rating; Contacts (locked rotor) 44.4 A @ 120 Vac; 22.2 A @ 240 Vac Alarm Load Ratings (pilot duty) 2 A @ 30 Vac Alarm Load Ratings (resistive) 2A @ 30 Vac Dimensions (in.) 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in. deep Temperature Range (F) -40 F to +147 F Temperature Range (C) -40 C to +64 C Approvals, Underwriters Laboratories Inc UL & CUL Component Recognized
|
|