Part-S-Mart: HVAC/R Parts  :: HVAC  :: Honeywell S86F1018 INTERMITTENT CONTROL

Honeywell S86F1018 INTERMITTENT CONTROL
Honeywell S86F1018 INTERMITTENT CONTROL 
Honeywell S86F1018. Honeywell S8610U3009 replaces Honeywell S86F1018

One or Two Rod Intermittent Pilot Control with continuous retry trial time with configurable lockout timing of 15 or 90 seconds and configurable prepurge of 30 seconds or no prepurge. Field service replacement for most Honeywell, Robertshaw, Johnson, and UTEC (HSC) Intermittent Pilot Ignition Modules. Provides electronic control of most intermittent pilot ignition systems used on gas-fired furnaces, boilers, and other heating appliances.

Provides ignition sequence, flame monitoring and safety shutoff for intermittent pilot central furnaces and heating appliances.

Provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated. Ignition trial/delay sequence is repeated until the appliance lights or call for heat is removed.

For use with Natural or LP gas.

For use in single rod or dual rod/remote sense applications. Includes relay contacts for use with any intermittent pilot gas control string with maximum 1.0A pilot or 2.0A main valve rating; Honeywell VR8204, VR8304 or VR8345M combination gas control recommended.

Functional equivalent of S86, S8600, S8610 and S90 modules.


Includes spark cable adapters to allow field replacement of both Honeywell and competitive controls without replacing existing spark cable.

Product Specifications

Description One or Two Rod Intermittent Pilot Control with continuous retry trial time with configurable lockout timing of 15 or 90 seconds and configurable prepurge of 30 seconds or no prepurge
Ignition System Type Intermittent Pilot
Ignition Sequence Continous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes place
Typical Gas Control VR8204, VR8304
Type of Gas Natural or LP
Flame Sense Single Rod or Two Rods
Ignition Source Internal high voltage spark generator
PrePurge Configurable to 30 seconds or no prepurge
Ignition Trials To Lockout continuous retry
Lockout Timing Configurable to 15 seconds or 90 seconds
Ignition Trial Time (sec) continuous retry
Maximum Valve Load @ 24 Vac (Amps) 1A Pilot, 2A Main @ 165 F; 1A Pilot, 1A Main @ 175 F
Typical Ignition Hardware Q345, Q3451, Q3452
Dimensions (in.) 3 15/16 in. high x 5 7/16 in. wide x 2 5/8 in. deep
Dimensions (mm) 100 mm high x 138 mm wide x 67 mm deep
Electrical Ratings 24 Vac
Frequency 50/60 Hz
Maximum Ambient Temperature (F) -40 F to +165 F
Maximum Ambient Temperature (C) -40 C to +74 C
Approvals, Canadian Standards Association Design Certified
Includes Damper connection with automatic vent damper plug
Tradeline Value Super Tradeline
Between Trial Time (sec) 5 minute delay after failed trial for ignition.
Flame Failure Response Time (sec) 2 seconds maximum

REPLACES: HONEYWELL S86F1018

  47%

Details
 
SKU HONS8610U3009-S86F1018
Weight 2.00 lbs
Stock Status Call to confirm the stock status of any item.
Availability Stock items ship same day if ordered by 4 p.m. CST, some items may be out of stock or non-stock and will be backordered and shipped when received.