Product Specifications SV9602P4824 Description 3/4 in. NPT x 3/4 in. NPT Intermittent Hot Surface Pilot Ignition SmartValve™ Control with step opening and Full Rate: 3.5 in. wc; Step Setting: 2.5 in. wc pressure regulator setting Flame Sense Two Rod Type of Gas Natural Ignition System Type Intermittent Hot Surface Pilot Ignition Ignition Sequence Intermittent Pilot Ignition Source Pilot Ignition Trials To Lockout continuous retry PrePurge 30 sec Body Pattern Straight-through Opening Characteristics (standard, step) Step Opening Control Voltage (Thermostat or other call for heat) 24 Vac, 60 Hz. Ignition Trial Time (sec) 90 sec Electrical Ratings 24 Vac Frequency 50 Hz Frequency 60 Hz Flame Failure Response Time (sec) 1.6 sec @ 3 µA Ambient Temperature Range (F) -40 F to +175 F Ambient Temperature Range (C) -40 C to +79 C Dimensions (in.) 3.2 in. wide x 4.9 in. high x 4.1 in.long Dimensions (mm) 81 mm wide x124 mm high x 104 mm long. Pressure Regulator Setting (psi) Full Rate: 3.5 in. wc; Step Setting: 2.5 in. wc Pressure Regulator Setting (kPa) Full Rate: 0.87 kPa; Step Setting: 0.62 kPa Inlet/Outlet Size (in.) 3/4 in. NPT x 3/4 in. NPT. Maximum Capacity (ft³/hr) 415 ft³/hr Maximum Capacity (m³/hr) 11.8 m³/hr Minimum Capacity (ft³/hr) 30 ft³/hr Minimum Capacity (m³/hr) 0.8 m³/hr Maximum Capacity at 1 in. P.D. (ft³/hr) 300 ft³/hr Maximum Capacity at 1 in. P.D. (m³/hr) 8.5 m³/hr Pressure Tapping 1/8 in. - NPT Mounting 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically. Approvals, Canadian Standards Association CSA-International,Design Certified Tradeline Value Tradeline
|
|